Line Differential Protection and Control
RED615
Product version: 2.0
Table 16. Electromagnetic compatibility tests
Description
1 MHz burst disturbance test:
• Common mode
• Differential mode
Electrostatic discharge test:
• Contact discharge
• Air discharge
Radio frequency interference
tests:
• Conducted, common mode 10 V (rms), f=150 kHz...80 MHz
• Radiated, amplitude-
modulated
• Radiated, pulse-modulated
Fast transient disturbance
tests:
• All ports
Surge immunity test:
• Binary inputs
• Communication
• Other ports
Power frequency (50 Hz)
magnetic field:
• Continuous
24
Type test value
2.5 kV
1.0 kV
8 kV
15 kV
10 V/m (rms), f=80...2700 MHz
10 V/m, f=900 MHz
4kV
4 kV, line-to-earth
2 kV, line-to-line
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
1MRS756500 B
Issued: 03.07.2009
Reference
IEC 61000-4-18 and IEC
60255-22-1, level 3
IEC 61000-4-2, IEC
60255-22-2 and IEEE
C37.90.3.2001
IEC 61000-4-6 and IEC
60255-22-6, level 3
IEC 61000-4-3 and IEC
60255-22-3, level 3
ENV 50204 and IEC
60255-22-3, level 3
IEC 61000-4-4 and IEC
60255-22-4, class A
IEC 61000-4-5 and IEC
60255-22-5, level 4/3
IEC 61000-4-8, level 5