ABB RED615 Product Manual page 30

Line differential protection and control
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Line Differential Protection and Control
RED615
Product version: 2.0
Table 27. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on
stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one phase with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
30
PHLPTOC
PHHPTOC
and
PHIPTOC
PHIPTOC:
I
= 2 x set Start
Fault
value
I
= 10 x set Start
Fault
value
PHHPTOC and
PHLPTOC:
I
= 2 x set Start
Fault
value
Value
Depending on the frequency of the current
measured: f
±2Hz
n
±1.5% of the set value or ±0.002 x I
±1.5% of set value or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0% of the set value
(at currents in the range of 10...40 x I
Minimum
Typical
16 ms
19 ms
11 ms
12 ms
22 ms
24 ms
< 40 ms
Typical 0.96
< 30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50dB at f = n x f
n
...
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1MRS756500 B
Issued: 03.07.2009
n
n
)
n
)
n
Maximum
23 ms
14 ms
25 ms
3)
, where n = 2, 3, 4, 5,
ABB

Advertisement

Table of Contents
loading

Table of Contents