ABB
Line Differential Protection and Control
RED615
Product version: 2.0
Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) main settings
Parameter
Start Value
Time multiplier
Operate delay time
Operating curve
1)
type
1) For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
Function
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHLPTOC
PHHPTOC
PHIPTOC
PHLPTOC
PHHPTOC
PHIPTOC
Value (Range)
Step
0.05...5.00 x I
0.01
n
0.10...40.00 x I
0.01
n
1.00...40.00 x I
0.01
n
0.05...15.00
0.05
0.05...15.00
0.05
40...200000 ms
10
40...200000 ms
10
20...200000 ms
10
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
Definite time
1MRS756500 B
Issued: 03.07.2009
31