Step 2.4 Optional: Extending the
power cable
1 Prepare the following tools.
Tools
Crimping
pliers
Connection
sleeve (mm)
Insulation
tape
Contraction
tube (mm)
2 As shown in the figure, peel off the shields from the
rubber or wire of the power cable.
Peel off 0.79inch(20mm) of cable shields from the
preinstalled tube.
CAUTION
For information about the power cable
specifications for indoor and outdoor units, refer to
the installation manual.
After peeling off cable wires from the preinstalled
tube, insert a contraction tube.
Power cable
0.79(20)
Pre-installed tube for the power cable
0.79(20)
3 Insert both sides of core wire of the power cable into
the connection sleeve.
Method 1: Push the core wire into the sleeve from
both sides.
Method 2: Twist the wire cores together and push
it into the sleeve.
Method 1
Connection sleeve
4 Using a compressor, compress the two points and flip
it over and compress another two points in the same
location.
42 English
IBIM_EN.indd 42
Spec
Shape
MH-14
(HxOD)
Width
0.71inch(18mm)
(LxOD)
0.79(20)
0.79(20)
2.36(60)
4.72(120)
7.09(180)
(Unit: inch(mm))
(Unit: inch(mm))
Method 2
Connection sleeve
The compression dimension should be 8.0.
After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
Compress it 4 times.
0.20inch(5mm)
5 Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
Three or more layers of insulation are required.
Method 1
Insulation tape
1.57inch(40mm)
6 Apply heat to the contraction tube to contract it.
Contraction tube
7 After tube contraction work is completed, wrap it with
the insulation tape to finish.
CAUTION
Make sure that the connection parts are not exposed
to outside.
Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials
that have the same level of withstand voltage with
the power cable. (Comply with the local regulations
on extensions.)
Compression
dimension
Method 2
Compress it 4 times.
0.20inch(5mm)
Method 2
Insulation tape
1.37inch(35mm)
Insulation tape