Outdoor Unit Installation

Step 3.1 Fixing the outdoor unit in
place
Rubber leg
Model
09/12
1 Place the outdoor unit as directed on the top of
the unit to let the discharged air out properly.
2 Fix the outdoor unit in level to an appropriate
support using anchor bolts.
NOTE
Secure the rubber legs to help prevent the
generation of noise and vibration.
If the outdoor unit is exposed to strong winds,
install shield plates around the outdoor unit so
that the fan can operate correctly.
Optional: Fixing the outdoor unit to a wall with a
rack
Soft rubber designed to cut off vibration from
rack to wall (not supplied with product)
Soft rubber designed to cut off residual vibration from
outdoor unit to rack (not supplied with product)
48 English
IBIM_EN.indd 48
X
(Unit : ft(mm))
X
Y
2.00 ft (612mm)
1.04ft (317mm)
NOTE
Make sure that the wall can support the weights
of the rack and the outdoor unit.
Install the rack close to the column as much as
possible.
Step 3.2 Connecting the power
and communication cables and the

refrigerant pipes

L1
L2
Outdoor-to-indoor power cable
Power cable
(three wires)
(three wires)
CAUTION
Be sure to fix the power cables and communication
cable with a cable clamp.
F1
F2
Communication cable
(two wires)