Capacity Range & Operating Limits (cont.)

Refrigerant Piping Limitations

A
B
Liquid Line
Max (feet)
Vertical
A
Drop
Between
B
IDU
Vertical
C
Rise
From 1st
D
Joint
(295)**
Linear
E
Length
Total
Network
* Setting adjustment on condensing unit required.
** Fan coil distance differentials need to be met
Possible refrigerant noise can be mitigated (via setting adjustments on ODU)
when linear length exceeds 390FT.
14
C
D
E
VRV-IV
VRV-IV
Heat
Heat
Pump
Recovery
164
164
(295)*
(295)*
100
100
(49)†
130
130
(295)*
(195)*
130
130
(295)**
540
540
3280
3280
VRV-IV
VRV
W-Series
Aurora
Water
Series
Cooled
164
164
(295)*
100
49
(49)†
130
130
(195)*
130
130
(295)**
(295)**
540
390
1640
980
VRV-IV S
VRV-IV S
(36)
(48-60)
98
98
33
49
98
98
130
130
164
230
820
984