Rated Technical Data; Sound Levels - Galletti AREO S 12 Technical Manual

Aero s series fan heater for steam operation
Table of Contents

Advertisement

AREO S
4

RATED TECHNICAL DATA

Fan
Model
Speed
rpm
4P
AREO S 12
6P
4P
AREO S 22
6P
4P
AREO S 32
6P
4P
AREO S 42
6P
4P
AREO S 52
6P
6P
AREO S 62
8P
Rated capacity determined at the following conditions:
Heating mode:
Steam pressure 1 bar (120°C), inlet air temperature 20°C
Sound pressure: distance of 5 meters, directional factor equal to 2
Fan speed:
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
8 p= 8 poles, 700 rpm
5

SOUND LEVELS

Legend:
Lp
A - weighted sound pressure level (5m distance, 2 directional factor)
A
Lw
Octave band sound power level
Lw
A - weighted sound power level
A
Vr
Fan speed:
4 p = 4 poles, 1400 rpm
6 p = 6 poles, 900 rpm
8 p= 8 poles, 700 rpm
MODEL
Vr
4P
AREO S 12
6P
4P
AREO S 22
6P
4P
AREO S 32
6P
4P
AREO S 42
6P
4P
AREO S 52
6P
6P
AREO S 62
8P
The technical and dimensional data reported in this manual may be modified in view of
any product improvement.
Air
Heating
Flow
Capacity
3
m
/h
kW
1150
12,00
700
8,92
2600
24,50
1650
18,80
4250
39,28
2700
30,19
5900
55,40
3750
42,55
8800
79,42
5600
61,18
8100
92,65
6250
79,34
125 Hz
250 Hz
500 Hz
dB
dB
dB
61,9
63,1
61,8
62,0
58,5
59,3
64,9
66,1
64,8
63,0
59,5
60,3
69,9
71,1
69,8
65,0
61,5
62,3
72,9
74,1
72,8
69,0
65,5
66,3
80,7
83,2
78,2
69,7
72,2
67,2
73,7
76,2
71,2
67,7
66,9
65,5
All copying, even partial, of this manual is strictly forbidden
Steam
Air Outlet
Flow
Temperature
kg
°C
20
51,0
15
57,9
40
48,0
31
53,9
64
47,5
49
53,2
90
47,9
69
53,7
130
46,8
100
52,5
151
54,0
129
57,7
Lw
1 kHz
2 kHz
4 kHz
dB
dB
dB
61,3
59,1
56,2
56,5
55,2
51,1
64,3
62,1
59,2
57,5
56,2
52,1
69,3
67,1
64,2
59,5
58,2
54,1
72,3
70,1
67,2
63,5
62,2
58,1
78,7
77,8
74,1
67,7
66,8
63,1
71,7
70,8
67,1
65,7
65,3
61,8
3
Max Installation
Sound
Height
Power
m
dB A
3,0
66
3,0
62
3,5
69
3,5
63
4,5
74
4,0
65
4,5
77
4,0
69
5,0
84
4,0
73
5,5
77
5,0
71
8 kHz
Lw
A
dB
dB/A
49,6
66
43,6
62
52,6
69
44,6
63
57,6
74
46,6
65
60,6
77
50,6
69
66,6
84
55,6
73
59,6
77
52,5
71
AP66000271 - 01
Weight
kg
19,4
25,1
33,7
39,1
49,6
58
Lp
A
dB/A
44
40
47
41
52
43
55
47
62
51
55
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Areo s 32Areo s 22Areo s 42Areo s 62Areo s 52

Table of Contents