Remote Control Function; Rated Technical Data - Galletti WH SERIES Technical Manual

High wall fan coil units
Table of Contents

Advertisement

WH
3

REMOTE CONTROL FUNCTION

REMOTE CONTROL FUNCTIONS
-
If the room temperature is lower than the setting temperature, the
heating mode is activated. The motor driven valve is triggered. The
internal fan works at the set speed.
-
If the room temperature is equal to the setting temperature + 0.5°C,
the heating mode is stopped. The motor driven valve and the internal
fan are disconnected.
-
The setting temperature range is 15° - 30°C.The internal fan speed can
be set on Min, Med, Max and Auto.
-
The motor driven valve will be activated/deactivated after a delay time of
30 sec
-
If the water temperature is equal to 38°C, the motor driven valve is
activated and the internal fan is deactivated.
-
If the water temperature is >38°C the motor driven valve is activated. The
internal fan will continue working at the set speed.
-
If the water temperature is >75°C the motor driven valve is deactivated.
The internal fan will continue working at the set speed.
4

RATED TECHNICAL DATA

Total cooling capacity
Sensible cooling capacity
Water flow
Water pressure drop
Heating capacity
Water flow
Water pressure drop
Water connection
Drain connection
Water content
Air flow
Power supply
Current absorption
Power input
Sound power level
Sound pressure level
Overall dimension: height
Overall dimension: lenght
Overall dimension: depth
Approx. weight
- Cooling mode: water temperature 7/12°C, air temperature 27°C dry bulb, 19°C wet bulb
- Heating mode: water temperature 70-60°C, air temperature 20°C
- Sound pressure calculated for 1 meter distance, under the unit
COOLING
-
If the room temperature is higher than the set temperature, the cooling
mode is activated. The motor driven valve is activated. The internal fan
works at the set speed.
-
If the room temperature is equal to the setting temperature -0.5°C, the
cooling mode is stopped. The motor driven valve is deactivated. The
internal fan works at the set speed.
-
The setting temperature range is 15° - 30°C.
-
The internal fan speed can be set on Min, Med, Max and Auto.
-
The motor driven valve will be activated/deactivated after a delay time of
30 sec.
-
If the water temperature is equal to or lower than 2°C, the motor driven
valve is deactivated and the internal fan continues working at the set
speed.
TIMER
-
The switch off timer can be set only when the system is ON.
-
The switch on timer can be set only when the system is OFF.
-
The maximum setting time is 24 hours.
-
Switching the unit on/off will cancel the timer mode.
Fan speed
kW
High
High
kW
l/h
kPa
High
kW
l/h
kPa
"
mm
dm
3
m
High
3
m
Med
3
m
Low
V / f / Hz
High
A
W
High
dB(A)
Med
dB(A)
Low
dB(A)
High
dB(A)
Med
dB(A)
Low
dB(A)
mm
mm
mm
kg
3
All copying, even partial, of this manual is strictly forbidden
WH10
WH20
2,27
3,06
1,72
2,41
389
524
15
13
5,34
7,87
468
685
15
18
1/2
1/2
22
22
3
0,5
1,1
/h
415
515
/h
360
460
/h
335
420
230 /1 / 50
230 /1 / 50
0,15
0,17
34
39
54
54
50
51
48
49
46
46
42
43
40
41
276
320
870
1020
183
185
12
15
WH30
4,28
3,15
734
18
9,96
873
19
1/2
22
1,8
750
630
570
230 /1 / 50
0,24
51
60
55
51
52
47
43
330
1160
213
18
SY66000120 - 03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents