Rated Technical Data - Galletti FM 22 Technical Manual

High wall-mounted fan coil units with bldc motor and incorporated valve 2.0 kw-3.7 kw
Table of Contents

Advertisement

FM
4

RATED TECHNICAL DATA

Model
Supply voltage
Speeds
Total cooling capacity (1)
Sensible cooling capacity (1)
Water flow rate (1)
Pressure drop (1)
FCEER - nominal value
FCEER - Class
Heating capacity (2)
Pressure drop (2)
FCCOP - nominal value
FCCOP - Class
Air flow rate
Power input
Sound power level (3)
Sound pressure level (4)
Water content
Water connections (female gas)
Condensate drainage connection
Dimensions H x L x P
Net weight
1 Water temperature 7-12°C, air temperature D.B. 27°C, W.B. 19°C (47% relative humidity)
2 Water temperature 50°C, water flow rate same as in cooling mode, air inlet temperature 20°C
3Sound power measured according to standards ISO3741 and ISO3744
4Sound pressure level measured at a distance of 1 m with a directivity factor of 4
FC66003740 - Rev 01
RATED TECHNICAL DATA OF FM FAN COIL UNITS
22 / 23
V - ph - Hz
1
2
kW
1,37
1,64
kW
0,99
1,20
l/h
234
281
kPa
11
15
168
B
kW
1,75
2,12
kPa
9
12
216
m3/h
290
370
W
8
10
dB/A
35
40
dB/A
27
32
dm3
0,43
inches
inches (mm)
mm
kg
12,00
All copying, even partial, of this manual is strictly forbidden
32 / 33
230-1-50 / 220-1-60
3
1
2
2,07
1,94
2,40
1,52
1,40
1,47
356
335
414
22
18
26
187
A
2,70
2,48
2,61
18
15
22
230
B
500
370
445
13
10
13
48
38
43
40
30
35
1/2
5/8 (16)
876/228/300
13,00
42 / 43
3
1
2
3,02
2,68
3,28
2,22
1,95
2,40
518
457
565
38
25
36
183
B
3,93
3,45
4,20
32
20
29
238
645
570
740
20
13
20
53
45
52
45
37
44
0,86
14,00
3
3,74
2,74
641
45
4,87
36
876
30
57
49
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fm 32Fm 23Fm 33Fm 42Fm 43

Table of Contents