Mode 2: Field Settings - Daikin LRMEQ3BY1 Installation And Operation Manual

Air-cooled refrigeration condensing unit
Hide thumbs Also See for LRMEQ3BY1:
Table of Contents

Advertisement

6 Configuration
6.1.8

Mode 2: Field settings

In mode 2 you can make field settings to configure the system. The LEDs give a binary representation of the setting/value number.
Setting
[2‑0]
T
target evaporating temperature.
e
With this setting the target evaporating temperature can be set in
increments of 5 K.
[2‑1]
T
fine‑tuning of evaporating temperature.
e
With this setting the target evaporating temperature set by [2‑0]
can be fine‑tuned in increments of 1 K.
[2‑6]
Address of the outdoor unit for communication with the Modbus
communication box (BRR9A1V1).
For more information, see the installation manual of the Modbus
communication box.
[2‑13]
Correction of evaporating temperature during low‑noise operation.
With this setting the target evaporating temperature set with
settings [2‑0] and [2‑1] can be corrected for low‑noise operation
(see setting [2‑18])
[2‑17]
Adjustment of fan and compressor speed during low‑noise
operation.
With this setting the maximum fan and compressor speed can be
set for low noise operation (see setting [2‑18]).
[2‑18]
Low noise operation
With this setting one of three low‑noise operation modes can be
selected. Low‑noise mode can be activated by turning ON the
contact between terminals X2M/A and X2M/B. Refer to settings
[2‑13] and [2‑17] to set parameters for the low‑noise levels.
INFORMATION
For LRMEQ3 outdoor units, low noise steps 2, 3, and 4
have the same sound reducing effect.
Installation and operation manual
22
(= binary)
Value
(default)
(default)
...
(default)
(default)
Correction of evaporating temperature (only
(default)
setting [2-13] applies)
Adjustment of fan and compressor speed (only
setting [2-17] applies)
Correction of evaporating temperature and
adjustment of fan and compressor speed (both
settings [2-13] and [2-17] apply)
Description
–10°C
–20°C
–15°C
–5°C
0°C
5°C
+0°C
+1°C
+2°C
+3°C
+4°C
Address not set
Address 1
Address 2
Address 3
Address 4
Address 5
...
Address 63
+1°C
+2°C
+3°C
+4°C
+5°C
+10°C
+15°C
+20°C
+0°C
+25°C
Low noise step 1
Low noise step 2
Low noise step 3
Low noise step 4
Low noise step 5
LRMEQ3+4BY1
Air-cooled refrigeration condensing unit
4P495373-1 – 2017.07