18 Configuration
[1‑2]
Shows the status of power consumption limitation operation.
[1‑2]
0
Unit is currently not operating under power
consumption limitations.
1
Unit is currently operating under power
consumption limitation.
[1‑5] [1‑6]
Code
Shows ...
[1‑5]
The current T
[1‑6]
The current T
[1‑10]
Shows the total number of connected indoor units.
[1‑17] [1‑18] [1‑19]
Code
Shows ...
[1‑17]
The latest malfunction code
[1‑18]
The 2nd last malfunction code
[1‑19]
The 3rd last malfunction code
[1‑40] [1‑41]
Code
Shows ...
[1‑40]
The current cooling comfort setting
[1‑41]
The current heating comfort setting
18.1.7

Mode 2: field settings

[2‑8]
T
target temperature during cooling operation.
e
[2‑8]
0 (default)
2
3
4
5
6
7
[2‑9]
T
target temperature during heating operation.
c
[2‑9]
0 (default)
1
2
3
4
5
6
[2‑20]
Manual additional refrigerant charge/SV/indoor unit connection
check
[2‑20]
0 (default)
Manual additional refrigerant charge
deactivated.
Installation and operation manual
42
Description
target parameter position
e
target parameter position
c
T
target [°C]
e
Auto
6
7
8
9
10
11
T
target [°C]
c
Auto
41
42
43
44
45
46
Description
[2‑20]
1
Manual additional refrigerant charge activated.
To stop the manual additional refrigerant
charge operation (when the required additional
refrigerant amount is charged), push BS3. If
this function was not aborted by pushing BS3,
the unit will stop its operation after 30 minutes.
If 30 minutes was not sufficient to add the
needed refrigerant amount, the function can be
reactivated by changing the field setting again.
2
Perform a SV/indoor unit connection check.
Perform a SV units and indoor units connection
check where for each indoor unit is checked if
the piping and communication wiring are
connected to the same branch pipe port.
[2‑22]
Automatic low noise setting and level during night time.
By changing this setting, you activate the automatic low noise
operation function of the unit and define the level of operation.
Depending on the chosen level, the noise level will be lowered. The
start and stop moments for this function are defined under setting
[2‑26] and [2‑27]. For more details about settings [2‑26] and [2‑27],
see installer user reference guide
[2‑22]
0 (default)
Deactivated
1
Level 1
2
Level 2
3
Level 3
4
Level 4
5
Level 5
[2‑35]
Height difference setting.
[2‑35]
0
In case the outdoor unit is installed in the
lowest position (indoor units are installed on a
higher position than outdoor units) and the
height difference between the highest indoor
unit and the outdoor unit exceeds 40 m, the
setting [2‑35] should be changed to 0.
1 (default)
[2‑45]
SV unit shut-off valve setting.
[2‑45]
0 (default)
Shut-off valve fully open
1
Shut-off valve fully closed
[2‑54]
Indoor unit connection setting.
[2‑54]
0 (default)
Direct connection to the outdoor unit is not
possible
1
Direct connection to the outdoor unit is allowed
[2‑60]
Supervisor remote controller setting. A power reset is required to
save this setting.
For details about the supervisor remote controller, see
requirements"  [ 4   19] or refer to the remote controller
layout
installation and user reference guide.
Description
Description
Level 5<Level 4<Level
3<Level 2<Level 1
Description
Description
Description
"13.2 System
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1B – 2024.02