Site Requirements; Table 2-1 Physical Specifications - HP A1896A Installation Manual

Cabinet for 9000 d-class enterprise servers
Table of Contents

Advertisement

2

Site Requirements

This chapter describes the site requirements for the installation of an HP A1896A or HP
A1897A cabinet. There is no HP site preparation required for the rack-mount cabinets.
There are some customer site preparation requirements. The customer is responsible for
having the proper type and amount of electrical outlets at the cabinet site. The customer
must also be aware of any system site requirements that the computer in the cabinet may
have. Be sure to check all site requirements before installing any equipment. Refer to
Table 2-1 for the cabinet physical specifications, and Table 2-2 for the cabinet electrical
requirements. Table 2-1 shows the types of receptacles that are needed to match the power
cords for specific cabinet power configurations.
NOTE
There are no special environmental site requirements for the HP A1896A or
HP A1897A cabinets, or the computer systems contained in them.
Table 2-1 Physical Specifications
Cabinet
All Models
A1897A
A1896A
Table 2-2 Power Requirements
Cabinet
A1896A
US 100-129V/50/60HZ, 16A max
(1.1 meter)
US 208-240V/50/60Hz, 16A max
Europe 230V/50/60Hz, 16A max
A1897A
US 208-240V/50/60Hz,16A max
(1.6 meter)
Europe 230V/50/60Hz,16A max
Refer to Figure 2-1 for the type of receptacle required to accommodate the cabinet power
cords.
Chapter 2
Width: 600 mm (23.6 in)
Depth: 905 mm (35.6 in)
Cooling and access space: 610 mm (24 in), front and rear
Height: 1.6 meter (63.8 inches)
Height: 1.1 meter (44.3 inches)
PDU V/A
specifications
Plug Type
Receptacle Type
NEMA 5-20P
NEMA 5-15
NEMA L6-20P
NEMA L6-20R
Cable no plug
Country dependent
NEMA L6-20P
NEMA L6-20R
Cable no plug
Country dependent
Site Requirements
# IEC 320
Outlets
6
10
10
10
10
2-1