ONE PHASE FAULT
OVERLOAD
40
Gamatronic Electronic Industries Ltd.
Meaning:One or more of the ac phases into the Charger is out of range.
Additional indications The alarm LED lights up and the audible alarm
sounds.
Action: This is likely to be due to a problem with the input ac supply.
Meaning:There is an overload condition.
Additional indications The alarm LED lights up and the audible alarm
sounds. If the output current is between 104 – 117%, for 10 minutes, or
between 117 – 131% for one minute, or above 131% for 20 msec, the UPS
shuts down. The symbol
Action: Reduce the load to the UPS quickly, or the UPS will automatically
move to Bypass mode.
appears on the Main Screen.