Power source
❇ 1
Cooling capacity
❇ 2
❇ 1
Heating capacity
Power consumption
Cooling
(50/60Hz)
Heating
Cooling
Current
Heating
External finish
Height
Dimension
Width
Depth
Net weight
Heat exchanger
Type
Airflow rate
Fan
(Lo-Hi)
External static pressure
Type
Motor
Output
Air filter
Gas
(Flare)
Refrigerant
pipe dimension
Liquid
(Flare)
Drain pipe dimension
❇ 3
Noise level (Lo-Mid-Hi)
❇ 1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Note:
Cooling : Indoor 27˚CDB/19˚CWB,Outdoor 35˚CDB
Heating : Indoor 20˚CDB,Outdoor 7˚CDB/6˚CWB
❇ 2 Cooling capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27˚CDB/19.5˚CWB,Outdoor 35˚CDB (WR2: water 30˚C)
❇ 3 It is measured in anechoic room.
PEFY-P100VMM-E
PEFY-P125VMM-E
~220-240V 50Hz
kW
11.2
kcal/h
10,000
kW
12.5
kW
0.29
kW
0.29
A
1.34
A
1.34
Galvanizing
mm
mm
1415
mm
kg
62
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan✕2
m
3
/min
23.0-33.0
28.0-40.0
Pa
Single phase induction motor
kW
0.200
PP Honeycomb fabric (washable)
ø
15.88 (R410A)
mm
ø
19.05 (R22,R407C)
mm
R1 (External thread)
dB(A)
40-44
1- 27
PEFY-P140VMM-E
14.0
16.0
12,500
14,000
16.0
18.0
0.40
0.42
0.40
0.42
1.90
1.95
1.90
1.95
325
1715
740
65
70
29.5-42.0
50/130
0.280
ø 9.52
42-45
42-45