No.
Name
1)
RUN LED
RUN
2)
CHANNEL selection
switch
CH
3)
OFF SET switch
OFF SET
4)
GAIN switch
GAIN
5)
Test mode terminal
TEST
The operation state of the A1S64AD is indicated.
Normal mode
ON
: In normal operation
Flickering: Write data error has occurred.
OFF
: 5V power OFF or watch dog timer error
Test mode
ON
: OFF SET switch or GAIN switch is ON
OFF
: OFF SET switch and GAIN switch are
both OFF
The channel for adjusting the offset and the gain is
selected.
(Channels other than 1 to 4 have no process.)
By setting the switch to the OFF SET side, the
analog input value at that time will be saved by the
A1S64AD as the offset value.
By setting the switch to the GAIN side, the analog
input value at that time will be saved by the
A1S64AD as the gain value.
Short-circuit across terminals 1 and 2 when setting
the offset or gain.