Download Print this page

Mitsubishi A1S64AD User Manual page 10

A/d converter module
Hide thumbs Also See for A1S64AD:

Advertisement

1)
Apply the voltage or current to be
set as the gain value.
V+
V
COM
For voltage
For current
A
Actually connected resistance value
Set the gain switch to "GAIN".
RUN
ON
Remarks
The offset value and gain value have the following meanings.
(1) The offset value is the analog input value (voltage or current) at which the digital
output value is "0".
(2) The gain value is the analog input value (voltage or current) at which the digital
output value is the following:
(a) 2000 (1/4000 resolution)
(b) 4000 (1/8000 resolution)
(c) 6000 (1/12000 resolution)
V+
I+
COM
GAIN
Adjust any other
channels?
Release the test mode terminal
(across 1-2).
TEST
End
YES
A
NO

Advertisement

loading