Chapter 5 iCOM Controller
The delay enabling determines whether the alarm will be displayed and the alarm menu is entered, Options include
'Yes' and 'No'.
The alarm type can be set to 'ALM' (alarm), 'WRN' (warning) and 'MSG' (message). They determine the alarm degree
of the corresponding event.
The alarm names are listed in Table 5-25.
Alarm/event
SN
name
S236
FOL
S237
LOA
S238
CF
S239
HRT
S240
LRT
S241
HRH
S242
LRH
S243
HTA
S244
LTA
S245
HHA
S246
LHA
S249
OL1
S250
OL2
S251
HP1
S252
HP2
S253
LP1
S254
LP2
S255
PD1
S256
PD2
S257
HT1
S258
HT2
S259
EHO
S262
WHE
S263
SMO
S264
WUF
S265
CPH

5.7.7 CALIBRATION

The CALIBRATION menu can calibrate sensors by setting offsets. The parameters are listed in Table 5-26. The
parameters are in pairs: the former is the calibrated value and the latter is the calculated value, or the sum of the
measured value and the calibrated value. This value is engaged in the calculation of control need.
Parameters
S602
RTN TEMP
S603
CAL TEMP
S604
RTN HUM
S605
CAL HUM
S606
DS1 NTC
S607
CAL DS1
S608
DS2 NTC
Table 5-25 Alarm name description
Description
Fan overload
Loss of airflow
Filter clogged
High room temp.
Low room temp.
High room hum.
Low room hum.
High temperature of sensor A
Low temperature of sensor A
High humidity of sensor A
Low humidity of sensor A
Compressor 1 overload
Compressor 2 overload
Compressor 1 high pressure
Compressor 2 high pressure
Compressor 1 low pressure
Compressor 2 low pressure
Compressor 1 pumpdown fails
Compressor 2 pumpdown fails
Digital scroll 1 high temperature
Digital scroll 2 high temperature
EL HEAT HIGH TEMP
Working hours exceeded
Smoke detected
Water under floor
Conderser pump high water
Table 5-26 Descriptions of CALIBRATION parameters
Default
Calibrated return air temperature. It can be set as a positive or negative value. Use the up
K
and down buttons to change the setting value, 0.1K at each step
Sum of the calibrated value and measured return air temperature. This value is compared
25°C
with the setting value as the system actual temperature and is engaged in the calculation
Calibrated return air humidity. It can be set as a positive or negative value. Use the up and
+0.0%
down buttons to change the setting value, 1% at each step
Sum of the calibrated value and measured return air humidity. This value is compared with
44.0%
the setting value as the system actual humidity and is engaged in the calculation
Calibrated digital scroll 1NTC. It can be set as a positive or negative or positive value. Use
+0.0K
the up and down buttons to change the setting value, 0.1K at each step
Sum of the calibrated value and return air humidity measured by digital scroll 1NTC
29°C
sensor. This value is engaged in the calculation
Calibrated digital scroll 2NTC. It can be set as a positive or negative value. Use the up and
+0.0K
down buttons to change the setting value, 0.1K at each step
Liebert.PEX2 Series Air Conditioner User Manual
Alarm/event
SN
name
S266
LOF
Loss of flow
S267
SGP
Standby glycol pump on
S268
STB
Standby unit on
S269
HUP
Humidifier problem
S270
NOC
No connection w/Unit1
S271
-
No connection w/UnitX
S272
LOP
LOSS OF POWER
S275
CI1
Customized input 1
S276
CI2
Customized input 2
S277
CI3
Customized input 3
S278
CI4
Customized input 4
S279
CS
Call for service
S280
HTD
High temperature
S281
LB1
Loss of air blower 2
S282
RL
Reheat lockout
S283
HL
Humidifier lockout
S284
FCL
FC lockout
S285
CL
Compressor(s) lockout
S288
SC1
Short cycle 1
S289
SC2
Short cycle 2
S290
NOP
NO power
S291
CN1
Condensor 1 Fail
S292
CN2
Condensor 2 Fail
S293
EFF
EC Fan fail
S294
HST
High supply air temperature
S295
LST
Low supply air temperature