8. TROUBLESHOOTING
Error
Error
Code
Detected
Slave
15
The enabled/privilege check failed
station
Slave
The requested service cannot be executed in the
16
station
current device status.
17
DN91
The slave station did not respond.
Slave
Insufficient data supplied after the designated
19
station
operations were conducted.
Slave
20
The designated attribute is not supported.
station
Slave
21
The service supplied more data than expected.
station
Slave
The designated object does not exist in the slave
22
station
station.
50
DN91
Incorrect response data format.
Designated slave station number is outside the
55
DN91
range 0 to 63.
57
DN91
Incorrect sequence during packet receipt.
No parameters set for the designated slave
200
DN91
station.
257
DN91
Data length set in buffer memory exceeds 241.
Incorrect value was set in command number of
258
DN91
buffer memory message communication
command area.
Details
8
12
Remedy
• Check if the designated station number, class ID,
instance ID, and attribute ID are correct.
• Refer to the slave station manual to determine the
conditions for the slave station to notify this error,
and take the appropriate remedy.
• Check if the designated station number, class ID,
instance ID, and attribute ID are correct.
• Refer to the slave station manual to determine the
conditions for the slave station to notify this error,
and take the appropriate remedy.
• Investigate overall status of network and slave
station. Is the slave station down, or the termination
resistance disconnected, for example?
• Check if the designated station number, class ID,
instance ID, and attribute ID are correct.
• For Set Attribute, check if the designated data is
insufficient and the data length is correct.
• Refer to the slave station manual to determine the
conditions for the slave station to notify this error,
and take the appropriate remedy.
• Check if the designated station number, class ID,
instance ID, and attribute ID are correct.
• Refer to the slave station manual to determine the
conditions for the slave station to notify this error,
and take the appropriate remedy.
• Set the data returned by the slave station to 240
bytes maximum.
• Check if the designated station number, class ID,
instance ID, and attribute ID are correct.
• Refer to the slave station manual to determine the
conditions for the slave station to notify this error,
and take the appropriate remedy.
• Investigate overall status of network and slave
station. Is the termination resistance disconnected,
for example?
• Designate from 0 to 63.
• Investigate overall status of network and slave
station. Is the termination resistance disconnected,
for example?
• Designate a slave station with set parameters.
• Set the data length 240 or less.