Table 6: Iecex Approvals - Honeywell RMA300-ME User Manual

Remote meter assemblies
Table of Contents

Advertisement

IECEx Approvals
Code
Description
CA
Certificate: LCI 08.0034X
Flameproof:
Ex d IIC Gb T6 (Ta= -40 to +65°C), T5 (Ta= -40 to +85°C)
Ex tb IIIC Db T95°C (Ta= -40 to +65°C) orT80°C (Ta= -40 to +85°C)
Intrinsically Safe:
Ex ia IIC Ga T4 (Ta= -40° to 85°C)
Intrinsic Safety Entity Parameters
VMax < 30 V
IMax = 100 mA
PMax = 1.2 W
Ci = 0 nF
Ci = 18 nF
Li = 0 µH
Li = 150 µH
Special Conditions of use:
All Protection Methods:
The enclosure is manufactured from low copper aluminum alloy. In rare cases, ignition sources due to impact and
friction sparks could occur. This shall be considered during Installation, particularly if equipment is installed a Zone
0 location.
For intrinsic safety protection:
The power terminals (+ and -) shall only be connected to associated intrinsically safe apparatus certified for the
intended use. This association shall comply with the requirements of the standard EN 60079-25.
WARNINGS and Cautions:
For intrinsic safety protection:
WARNING – DO NOT OPEN WHEN ENERGIZED
WARNING – AFTER DE-ENERGIZING, DELAY 1 MINUTES BEFORE OPENING
34

Table 6: IECEx Approvals

Class I, II, III, Divisions 1 and 2,
Groups A - G
WITH EU and ME Meters
WITH SM Meter
WITH EU and SM Meters
With Analog Meter, option ME
RMA 3000 Remote Meter Assemblies User Manual
Release 8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rma 3000Rma300-euRma300-smRma300-dm