INSTALLATION
INNER DOOR
Figure 4
Mounting The PMI/PMI-REMPMI-INTL
To The Rear Of The Inner Door
Siemens Building Technologies
Fire Safety
Remove ELECTRICAL POWER prior to installing the PMI/PMI-REM/PMI-INTL in the enclosure.
Remove the PMI from its anti static bag. Set the three-digit network address using the
10-position rotary switches located on the back of the PMI. For HNET, set the PMI/PMI-
REM/PMI-INTL to 253. Make sure that the PMI is configured at this address in the
Zeus physical view.
When the PMI is used with XNET, the three-digit network address switch is used to
set the XNET node address. In order to configure the PMI for XNET operation, first set
position 4 of the options switch, S17 , to ON. (Refer to Figure 2 for the location of the
options switch.) Next set the XNET node address that has assigned in Zeus on the
network address switches. Be sure to set all leading zeros. For example, Node 2 is
set at 002. The MNET address of the PMI is automatically set to 253 when position 4
of S17 is in the ON position.
Note the location of the contrast pot. Although the PMI comes from the factory with
the LCD contrast adjusted, this adjustment may not be proper for the viewing angle
of the LCD once it is installed in the enclosure. If the contrast appears poor with the
system powered, open the inner door and locate the contrast pot on the lower edge
of the PMI printed circuit board. Adjust this pot until the LCD contrast is acceptable.
The PMI/PMI-INTL mounts to the rear of the inner door in the
CAB-1, CAB-2 or CAB-3 enclosures. The PMI-REM/PMI-INTL
mounts to the rear of the inner door in the REMBOX2 or
REMBOX4 enclosures. Select the location of the PMI. They
can be mounted either in the center or on the left side of the
inner door, when viewed from the outside of the enclosure.
PMI
Place the PMI onto the inner door from the rear, over the four
mounting studs in the desired location. Secure the PMI to the
inner door with the four nuts provided. (Refer to Figure 4.)
A 40 inch long 60 wire cable, P/N 555-133743, connects the
PMI/PMI-INTL to the CC-5. The CC-5 is located in the back of
the enclosure on the left hand side. Connect one end of the
cable to JP3 on the PMI. JP3 is marked with "CC-5" on the
PMI/PMI-INTL printed circuit board. Connect the other end of
the cable to P1 on the CC-5. (Refer to Figure 5.)
A 24 inch long 60 wire cable, P/N 555-133998, connects the
PMI-REM to the RNI. The RNI is located in the back of the
enclosure on the top left hand side. Connect one end of the
cable to JP3 on the PMI-REM. JP3 is marked with "CC-5" on
the PMI-REM printed circuit board. Connect the other end of
the cable to P2 on the RNI. (Refer to Figure 6.)
The PMI-INTL also connects to the RNI, however it is shipped with a 40 inch long 60
wire cable, P/N 555-133743.
Make sure that all cables snap fully into their connectors and close the locking levers
over the top of each cable connector. Secure the cable in the back box using cable
ties and the tie down points in the enclosure. The cable must have sufficient slack to
allow the inner door to open fully without putting stress on the cable.