10-5 SIMULTANEOUS OPERATION SYSTEM INDIVIDUAL SETTING
It is easier if the optional remote controller is used when setting the slave unit.
Procedure
• Perform the following procedure when setting the master and slave unit separately. (Refer to Fig. 29)
(1) Change the SECOND CODE NO. to "02", individual setting, so that the slave unit can be individually set.
(Refer to Table 9)
(SECOND CODE NO. is factory set to "01", for unified setting.)
Table 9
Setting
Unified setting
Individual setting
NOTE
• The "Mode No." is normally set collectively for a group. In order to set each indoor unit individually and per-
form checks after the settings, specify the Mode No. in parenthesis.
(2) Perform field setting (Refer to 10-1 to 10-4) for the master unit.
(3) Turn off the main power supply switch after (2) is finished.
(4) Detach remote controller from the master unit and connect it to the slave unit.
(5) Turn on the main power supply switch again, and as in (1), change the SECOND CODE NO. to "02", indi-
vidual setting.
(6) Perform field setting (Refer to 10-1 to 10-3) for the slave unit.
(7) Turn off the main power supply switch after (6) is finished.
(8) If there is more than one slave unit, repeat steps (4) to (7).
(9) Detach the remote controller from the slave unit after the setting, and reattach to the master unit. This is
the end of the setting procedure.
* You do not need to rewire the remote controller from the master unit if the optional remote controller for
slave unit is used.
(However, remove the wires attached to the remote controller terminal board of the master unit.)
After the slave unit setting, remove the remote controller wiring, and rewire the remote controller from the
master unit.
(The unit does not operate properly when two or more remote controllers are attached to the unit in the
simultaneous operation system mode.)
Main power supply
Earth leakage
( 3 ) ( 7 )
circuit breaker
Outdoor unit
NOTE)
1 2 3
Indoor unit (Master)
NOTE
• Terminal numbers of outdoor and indoor units must agree.
English
Mode No.
11 (21)
1 2 3
P
P
1
2
Indoor unit (Slave)
Remote controller
P
P
1
2
( 1 ) ( 2 )
FIRST CODE NO.
1
Main power supply
Earth leakage
circuit breaker
Outdoor unit
1 2 3
NOTE)
1 2 3
1 2 3
P
P
1
2
Indoor unit (Master)
( 4 )
( 8 )
Fig. 29
SECOND CODE NO.
01
02
1 2 3
P
P
1
2
Indoor unit
(Slave)
Remote controller
P
P
1
2
P
P
1
2
( 5 ) ( 6 )
21