Field Setting - Daikin FAA71AUVEB Installation Manual

Split system air conditioner
Hide thumbs Also See for FAA71AUVEB:
Table of Contents

Advertisement

MAIN/SUB CHANGEOVER
• Refer to the manual attached to the remote controller.
Wiring Method
(1) Remove the control box lid.
(2) Add wiring between the remote controller 2 (Sub) and the terminal (P1, P2) of the terminal block (X1M) for
the remote controller in the control box. (There is no polarity.)
P1 P2 F1 F2
Remote
controller 1
(Main)
* For simultaneous operation system, be sure to
connect the remote controller to the master unit.
NOTE
• Terminal numbers of outdoor and indoor units must be matched.

10. FIELD SETTING

Complete all the "1. Items to be checked after completion of work" on page 4.
• Make sure that the installation and wiring work for the indoor and outdoor units is all completed.
• Make sure that the following items are all closed: the control box lid of the indoor unit and the outer board
and piping cover of the outdoor unit.
<Field setting must be made from the remote controller in accordance with the installation conditions.>
• Setting can be made by changing the "Mode No.", "FIRST CODE NO.", and "SECOND CODE NO.".
• For setting procedures and instructions, see the manual provided with the remote controller.
NOTE
• The "Mode No." is normally set collectively for a group. In order to set each indoor unit individually and per-
form checks after the settings, specify the Mode No. in parenthesis.
• Do not perform settings that are not listed in the table.
10-1 AIRFLOW SETTINGS WHEN THERMOSTAT IS OFF
• Set the flow rate according to the requirement of the environment after consultation with the customer.
(As the factory setting, airflow for when cooler thermostat is off is set to SECOND CODE NO. "02", while
other settings are set to "01".) (Refer to Table 5)
Table 5
Fan operation when thermo-
stat is OFF (Cooling/Heating)
Airflow rate when cooler ther-
mostat is OFF
Airflow rate when heater
thermostat is OFF
English
Terminal block
(X1M)
( Master *)
Additional
remote controller
Remote
controller 2
(Sub)
Setting
Normal
Stop
LL airflow rate
Setting airflow rate
LL airflow rate
Setting airflow rate
FIRST
Mode No.
CODE NO.
11 (21)
12 (22)
12 (22)
are the settings when shipped from the factory.
SECOND
CODE NO.
01
2
02
01
6
02
01
3
02
19