Troubleshooting
4.18 Position Sensor Abnormality
H6
Error Code
A compressor start-up failure is detected by checking the compressor running condition through
Method of Error
the position detection circuit.
Detection
If the error repeats, the system is shut down.
Error Decision
Reset condition: Continuous run for about 11 minutes without any other error
Conditions
Power supply voltage is not as specified.
Supposed
Disconnection of the compressor harness
Causes
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is outside the specified range.
71
SiBE041525F
Service Diagnosis