4.22 Output Overcurrent Detection

L5
Error Code
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Method of Error
Detection
 A position signal error occurs while the compressor is running.
Error Decision
 A rotation speed error occurs while the compressor is running.
Conditions
 An output overcurrent signal is fed from the output overcurrent detection circuit to the
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 11 minutes without any other error
 Poor installation condition
Supposed
 Closed stop valve
Causes
 Defective power module
 Wrong internal wiring
 Abnormal power supply voltage
 Defective outdoor unit PCB
 Power supply voltage is not as specified.
 Defective compressor
77
microcomputer.