Troubleshooting
4.10 OL Activation (Compressor Overload)
E5
Error Code
A compressor overload is detected through compressor OL.
Method of Error
Detection
If the error repeats, the system is shut down.
Error Decision
Reset condition: Continuous run for about 60 minutes without any other error
Conditions
Disconnection of discharge pipe thermistor
Supposed
Defective discharge pipe thermistor
Causes
Disconnection of connector S40
Disconnection of 2 terminals of OL (Q1L)
Defective OL (Q1L)
Broken OL harness
Defective electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
61
SiBE041525F
Service Diagnosis