Wire the Fingersafe Terminal Block
When wiring the terminal block, keep the fingersafe cover in place.
1. Loosen the terminal screws to be wired.
2. Route the wire under the terminal pressure plate.
You can use the bare wire or a spade lug. The terminals accept a 6.35 mm (0.25 in.) spade
lug.
TIP
The terminal screws are non-captive. Therefore, it is possible to use a ring lug [maximum 1/4-
inch o.d. with a 0.139-inch minimum i.d. (M3.5)] with the module.
3. Tighten the terminal screw, making sure that the pressure plate secures the wire.
Recommended torque when you tighetn terminal screws is 1.27 N•m (11.24 lb•in).
TIP
If you must remove the fingersafe cover, insert a screwdriver into one of the square wiring
holes and gently pry the cover off. If you wire the terminal block with the fingersafe cover
removed, you cannot put it back on the terminal block because the wires are in the way.
Wire Size and Terminal Screw Torque
Each terminal accepts as many as two wires with the following restrictions.
Wire Type
Solid
Cu-90 °C (194 °F)
Rockwell Automation Publication 1769-IN028C-EN-P - August 2016
Wiring the
Fingersafe
Terminal Block
Wire Size
2
2.5 mm
(14 AWG)
Compact I/O Expansion Power Supplies
Terminal Screw Torque
1.27 N•m (11.24 lb•in)