Parameters - Siemens 6ES7134-4NB01-0AB0 Manual

Simatic et 200s distributed i/o analog electronic module
Table of Contents

Advertisement

Parameters

2.1
Parameters
Table 2-1
Parameters for analog input module
2AI TC HF
Group diagnostics (parameter assignment error,
internal error)
Diagnostics: Overflow/underflow
Diagnostics: Wire-break check
Smoothing
Temperature unit
Comparison point
Type/range of measurement
Only with thermocouples. A parameter assignment error occurs when the wire break diagnostics are enabled in the
*
voltage measuring range. The module does not start up.
2AI TC HF analog electronic module (6ES7134-4NB01-0AB0)
Manual, 04/2007, A5E01076892-01
*
Range of values
Disable
Enable
Disable
Enable
Disable
Enable
None
Weak
Medium
Strong
Celsius
Fahrenheit
None
Yes (i.e., internal)
Deactivated
Voltage ±80 mV
TC-EL Type T (Cu-CuNi)
TC-EL Type K (NiCr-Ni)
TC-EL Type B (PtRh-PtRh)
TC-EL Type C (WRe-WRe)
TC-EL Type N (NiCrSi-NiSi)
TC-EL Type E (NiCr-CuNi)
TC-EL Type R (PtRh-Pt)
TC-EL Type S (PtRh-Pt)
TC-EL Type J (Fe-Cu-Ni)
TC-EL Type L (Fe-Cu-Ni)
Default setting
Applicability
Disable
Module
Disable
Module
Disable
Channel
None
Channel
Celsius
Module
None
Channel
TC-EL Type K
Channel
(NiCr-Ni)
2
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

2ai tc hf

Table of Contents