Omron 3G3MX2 Quick Start Manual page 31

Born to drive machines; 200 v class three-phase input 0.1 to 15 kw; 200 v class single-phase input 0.1 to 2.2 kw; 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

MX2 Quick Start Guide
Option
Terminal
Code
Symbol
31
FBV
PID Second Stage Output
32
NDc
Network Disconnect Detect
33
LOG1
Logic Output Function 1
34
LOG2
Logic Output Function 2
35
LOG3
Logic Output Function 3
39
WAC
Capacitor Life Warning Sig-
nal
40
WAF
Cooling Fan Warning Signal
41
FR
Starting Contact Signal
42
OHF
Heat Sink Overheat Warning
43
LOC
Low load detection
44
MO1
General Output 1
45
MO2
General Output 2
46
MO3
General Output 3
50
IRDY
Inverter Ready Signal
51
FWR
Forward Rotation
52
RVR
Reverse Rotation
53
MJA
Major Failure Signal
54
WCO
Window Comparator for
Analog Voltage Input
55
WCOI
Window Comparator for
Analog Current Input
58
FREF
Frequency Command
Source
59
REF
Run Command Source
60
SETM
2nd motor Selection
62
EDM
STO (Safe Torque Off) Per-
formance Monitor
(Output terminal 11 only)
63
OPO
Option card output
255
no
Not used
In the same way of that the digital inputs is possible to choose between normally close and normally open and even is possible to
use some On and Off delay for each of the outputs.
28
Input Function Summary Table
Function Name
ON
OFF
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
Parameter
Parameter name
Output [11] function
C021
[EDM assignable]
C022
Output [12] function
C026
Alarm relay function
C031
Output [11] active state
C032
Output [12] active state
C036
Alarm relay active state
C130
Output [11] on delay
C131
Output [11] off delay
C132
Output [12] on delay
C133
Output [12] off delay
C140
Relay output on delay
C141
Relay output off delay
C132
Output [12] on delay
C133
Output [12] off delay
Intelligent output
d006
terminal status
Description
Transitions to ON when the inverter is in RUN Mode and the PID Process Vari-
able (PV) is less than the Feedback Low Limit (C053)
Transitions to OFF when the PID Process Variable (PV) exceeds the PID High
Limit (C052), and transitions to OFF when the inverter goes from Run Mode to
Stop Mode
When communications watchdog timer (period specified by C077) has time out
When the Boolean operation specified by C143 has a logical "1" result
When the Boolean operation specified by C146 has a logical "1" result
When the Boolean operation specified by C149 has a logical "1" result
Lifetime of internal capacitor has expired.
Lifetime of cooling fan has expired.
Either FW or RV command is given to the inverter
No FW or RV command is given to the inverter, or both are given to the inverter
Temperature of the heat sink exceeds a specified value (C064)
Motor current is less than the specified value (C039)
General output 1 is ON (Used by Drive programing)
General output 2 is ON (Used by Drive programing)
General output 3 is ON (Used by Drive programing)
Inverter can receive a run command
Inverter is driving the motor in forward direction
Inverter is driving the motor in reverse direction
Inverter is tripping with major failure
Analog voltage input value is inside of the window comparator
Analog current input value is inside of the window comparator
Frequency command is given from the operator
Run command is given from the operator
2nd motor is being selected
STO is being performed
(output terminal for option card)
Description
Programmable functions available for logic
(discrete) outputs transistor type
Programmable functions available for logic
(discrete) outputs relay type
Select logic conversion, two option codes:
00... normally open [NO]
01... normally closed [NC]
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
Set range is 0.0 to 100.0 sec.
ON
OFF
Relay 12 11
MX2 Quick Start Guide