wattstopper DW 100 Installation Instructions Manual page 2

Table of Contents

Advertisement

Available languages

Available languages

Model #
DW-200
Presentation Mode
Presentation Mode is a feature of the Auto ON mode. When both relays are manually turned OFF the DW holds the lights OFF until no
motion has been detected for the duration of the Time Delay. With subsequent occupancy, the DW turns the load ON. If both relays are
ON and one relay is manually turned OFF this relay remains OFF until both the Time Delay and retrigger delay expires for the relay that
is ON, after that time the ON Mode control settings again apply.
Time Delays
The DW sensor holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP switch
settings. In the DW-200, both relays use the same delay.
Test/20 min
(DIP 1 & 2 OFF)
Time Delay
(15 min. DIP 1 ON & 2 OFF)
Walk-Through Mode
The Walk-Through mode shortens the time delay to reduce the amount of time the load is ON after a brief moment of occupancy, such
as returning to an office to pick up a forgotten item then immediately exiting.
Walk-Through Mode
(DIP #3 ON)
No Walk-Through
(DIP #3 OFF)
PIR Sensitivity Adjustment
The DW sensor constantly monitors the controlled environment and automatically adjusts the PIR to avoid common ambient conditions
that can cause false detections, while providing maximum coverage.
High
(DIP #4 OFF)
Low, 50%
(DIP #4 ON)
Alerts
The DW can provide audible alerts as a warning before the load turns OFF.
Audible Alerts
(DIP #7 ON)
No Alerts
Trigger Mode
The DW sensor has four occupancy trigger options, set with DIP switches 5 and 6. Determine the
appropriate option using the Trigger matrix.
In the Trigger Mode DIP switch setting table, in order to deem the area occupied:
• Both requires motion detection by the PIR and the Ultrasonic.
• Either requires motion detection by only one technology.
• PIR requires motion detection by the PIR.
Initial Occupancy: The method that activates a change from "Standby" (area unoccupied and load
OFF) to "Occupied" (area occupied and load may turn ON).
Maintain Occupancy: The method indicating that the area is still occupied and the lights should remain ON.
Re-trigger: In Auto On Mode, after the load turns off, detection by the selected technology within 5 seconds turns the lights back ON. If
the load was turned ON with the ON/OFF button, the re-trigger time is 30 seconds.
Relay
Default ON Mode
1
Auto ON
Manual ON
2
A Test Mode with a short time delay of five seconds is set when DIP switches 1 & 2 are OFF. It cancels
automatically after ten minutes, or when you set a fixed time delay. When the Test Mode times out, the
sensor will assume a 20 minute time delay. To restart Test Mode, change the time delay setting to any
fixed amount and then return it to the Test setting.
Time delays of 5, 15 (default), or 30 minutes are available. See DIP SWITCH SETTINGS for
information.
The DW sensor turns the load OFF 3 minutes after the area is initially occupied, if no motion is
detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay
applies.
Walk-Through mode disabled.
Default setting. Suitable for most applications.
Reduces sensitivity by approximately 50%. Useful in cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and where heat sources cause unnecessary activation.
Unit will beep at one minute, at 30 seconds and at 10 seconds before turning OFF load. When
Walk-Through is active, the unit beeps three times at 10 seconds before the load goes OFF.
No warnings provided.
DIP Switch #
Setting
8
OFF
ON
9
2
DIP
Trigger
Switch
Mode
5 6
Standard
Both
Either
Either
Option A
PIR
Either Either
Option B
PIR
PIR
PIR
Option C
Both
Both
Both
=ON
=OFF