Cooling Capacities - 25 Ton (Dm300) Cfm - York SUNLINE 2000 Technical Manual

Hide thumbs Also See for SUNLINE 2000:
Table of Contents

Advertisement

036-21060-004-A-1102
TABLE 4: COOLING CAPACITIES - 25 TON (DM300) CFM
OD Dry Bulb - 80.0
Air On
Evaporator
Coil
Total
Power
Input
1
Cap
2
MBH
kW
CFM
WB
73
368
24.8
68
341
24.0
10000
63
322
23.5
57
322
23.5
73
362
24.6
68
334
23.9
9000
63
311
23.2
57
310
23.2
73
357
24.5
68
328
23.8
8000
63
300
23.0
57
299
23.0
1. These capacities are gross ratings. For net capacity deduct the heat of the supply air blower motor MBH = 3.415 x kW. Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors and the compressor motors, but not the supply air blower motor.
Unitary Products Group
1
Sensible
Capacity
Total
Cap.
Entering Dry Bulb °F
MBH
88
82
77
72
233
173
113
-
346
309
243
180
120
321
322
320
252
187
306
322
320
301
258
305
219
164
110
-
341
287
228
171
116
315
311
296
236
178
295
310
309
291
242
295
204
155
106
-
336
266
213
162
113
308
300
274
221
169
285
299
298
281
227
284
Temperature of Air on Condenser Coil
OD Dry Bulb - 95.0
1
Sensible
*Capacity
Power
Input
Entering Dry Bulb °F
1
2
kW
88
82
77
27.3
229
168
108
26.4
304
237
175
25.9
306
303
245
25.8
305
302
284
27.1
214
158
105
26.2
282
222
166
25.5
294
285
229
25.5
294
292
274
26.9
200
150
101
26.0
260
208
157
25.1
285
268
214
25.1
284
282
265
OD Dry Bulb - 115.0
Sensible
Total
Power
Cap.
Input
Entering Dry Bulb °F
1
2
MBH
kW
72
88
82
-
300
32.0
213
155
114
283
31.2
283
220
181
268
30.5
268
265
251
268
30.5
268
265
-
295
31.8
200
144
111
275
30.7
261
206
172
259
30.0
259
258
236
258
30.0
258
258
-
291
31.6
186
137
107
266
30.3
244
192
163
250
29.5
250
248
221
249
29.5
249
248
1
Capacity
77
72
96
-
162
103
227
162
247
230
93
-
151
96
213
155
241
216
89
-
141
93
199
148
230
203
13