Mounting
7.3 Assembly and disassembly with different mounting systems
Mounting the reversing starter (size S2)
The figure below shows the work steps for mounting the reversing starter in screw-type
connection system (size S2).
①
Hook the pre-assembled feeder into the upper hooking position of the motor starter protector, and swivel the feeder
to the busbar adapter.
②
Press the locking device on the contactor down with a screwdriver.
③
Push the feeder onto the DIN rail of the busbar adapter.
④
Screw the contactor tight diagonally into the mounting plate openings provided using two M4 screws.
Tightening torque: 1.2 ... 1.5 Nm
⑤
Insert the connecting cables into the corresponding main conductor terminals. Screw the main conductor terminals
tight.
Figure 7-46
Mounting on the busbar adapter (reversing starter, screw-type connection system, size S2)
106
SIRIUS - SIRIUS 3RA load feeders
Manual, 09/2016, A5E03656507520A/RS-AB/003