5.8 INPUTS AND OUTPUTS
These settings specify how the direct input information is processed. The
assign a descriptive name to the direct input. The
specified direct input is driven by the device identified here.
The
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
The
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
Setting
DIRECT INPUT 1 DEFAULT STATE
Setting
DIRECT INPUT 1 DEFAULT STATE
Setting
DIRECT INPUT 1 DEFAULT STATE
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 1. When communication resumes, the input becomes fully operational.
Setting
DIRECT INPUT 1 DEFAULT STATE
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 0. When communication resumes, the input becomes fully operational.
b) DIRECT OUTPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT OUTPUT
5
The
DIRECT OUT 1 NAME
the FlexLogic operand that determines the state of this direct output.
c) APPLICATION EXAMPLES
The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued
below to illustrate usage of the direct inputs and outputs.
EXAMPLE 1: EXTENDING INPUT/OUTPUT CAPABILITIES OF A T60 RELAY
Consider an application that requires additional quantities of digital inputs or output contacts or lines of programmable logic
that exceed the capabilities of a single UR-series chassis. The problem is solved by adding an extra UR-series IED, such
as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are connected via
single-channel digital communication cards as shown below.
Figure 5–155: INPUT AND OUTPUT EXTENSION VIA DIRECT INPUTS AND OUTPUTS
Assume contact input 1 from UR IED 2 is to be used by UR IED 1. The following settings should be applied (Direct Input 5
and bit number 12 are used, as an example):
UR IED 1:
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
5-284
DIRECT INPUT 1 DEVICE ID
is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
. This corresponds to the direct output number of the sending device.
represents the state of the direct input when the associated direct device is offline. The
to "On" value defaults the input to Logic 1.
to "Off" value defaults the input to Logic 0.
to "Latest/On" freezes the input in case of lost communications. If the latest
to "Latest/Off" freezes the input in case of lost communications. If the latest

DIRECT OUTPUTS
1
DIRECT OUT
Dir Out 1
DIRECT OUT
MESSAGE
Off
DIRECT OUTPUT
MESSAGE
EVENTS: Disabled
setting allows the user to assign a descriptive name to the direct output. The
UR IED 1
UR IED 2
= "2"
= "12"
T60 Transformer Protection System
DIRECT INPUT 1 NAME
represents the source of direct input 1. The
DIRECT OUTPUT 1(32)
Range: up to 12 alphanumeric characters
1 NAME:
Range: FlexLogic operand
1 OPERAND:
Range: Enabled, Disabled
1
TX1
RX1
TX1
RX1
UR IED 2:
DIRECT OUT 12 OPERAND
5 SETTINGS
setting allows the user to
is
DIR OUT 1 OPERAND
= "Cont Ip 1 On"