5.4 SYSTEM SETUP
Table 5–10: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
as above
as above
as above
as above
IEC61850-90-5 AGGREGATOR 1 CONFIGURATION
PMU AGGREGATOR1: NAME: A user-defined visible string of characters (max. 56) to identify the source of the
stream. This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the
IEC61850 MSVID filed in the output stream.
PMU AGGREGATOR1: UDP: This setting selects the UDP port number that is used by this dataset for network report-
ing. Default setting values for C37.118 and IEC6150-90-5 are provided.
PMU AGGREGATOR1: #OF ASDUs: This setting sets the number of ASDU's per from 1 through to 4. Refer to the
table below.
Table 5–11: # OF ASDU
SETTINGS FOR # OF ASDU
1
5
2
3
4
m) CONTROL BLOCKS

PATH: SETTINGS
SYSTEM SETUP
 IEC 90-5 MSVCB
 CONFIGURATION
5-134
OPERAND SYNTAX
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
TRANSMISSION
ASDU at T0 (current values)
ASDU at T-1 (previous values) + ASDU at T0 (current values)
values)+ ASDU at T-2 (previous values) + ASDU at T-1 (previous ASDU at T0 (current
values)
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous
values)+ASDU at T0 (current values)
PHASOR MEASUREMENT UNIT
MSVCB 1 SVENA:
OFF
MSVCB 1 CLIENT CTRL:
MESSAGE
OFF
MSVCB 1 SVENA DEFLT:
MESSAGE
OFF
MSVCB 1 CONFREV:
MESSAGE
1
MSVCB 1 PRIORITY:
MESSAGE
4
MSVCB 1 IP CLASS:
MESSAGE
46
MSVCB 1 VID:
MESSAGE
0
MSVCB 1 APPID:
MESSAGE
0
T60 Transformer Protection System
OPERAND DESCRIPTION
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.

IEC 90 – 5 MSVCB01 CONFIGURATION
Range: Flexlogic Operand
Default: Off
Range: Flexlogic Operand
Default: Off
Range: Flexlogic Operand
Default: Off
Range: 1 to 4294967295
Default: 1
Range: 0 to 7
Default: 4
Range: 0 to 252
Default: 46
Range: 0 to 4095
Default: 0
Range: 0 to 16383
Default: 0
5 SETTINGS