Product liability ........7 Disposal ..........7 Overvoltage and lightning protection ..........7 Description of functions of the multicomp F144-3PH .... 8 Connecting the multicomp ...10 Installation and assembly ....10 Current transformer connection: 11 Connection diagram ......12 Terminal assignment ......13...
Page 3
KBR multicomp F144-3PH Setting transformer ratio ....23 Technical data multicomp F144-3PH .......47 Menu overview ........25 Measuring and display values ..47 Main menu cos φ .......28 Measuring accuracy ......48 4.6.1 Main menu voltage / current ..30 Measuring principle ......48 4.6.2 Main menu temperature ....31 Device memory........48...
KBR multicomp F144-3PH Table of contents Introduction Thank you for choosing this KBR quality product. To familiarize yourself with device operation and configuration, we recommend you read this manual carefully. This will enable you to make use of the entire range of functions that this high-quality product offers.
Introduction KBR multicomp F144-3PH Explanation of safety relevant symbols These operating instructions contain notes that must be observed for your personal safety and to avoid damage to equipment. These notes are identified by a warning sign or information symbol, depending on the degree of hazard they represent.
KBR multicomp F144-3PH Introduction Safety notes In order to prevent operating errors, device operation is kept as simple as pos- sible. This will enable you to start your device up quickly. In your own interest, however, the following safety notes should be read care- fully.
Each device is subject to long-term testing before it is delivered. For details on product liability, please refer to our general terms and conditions for electronic equipment, which you can find at www.kbr.de. The warranty on device properties applies only if the device has been operated...
Range of functions Description of functions of the multicomp F144-3PH The multicomp F144-3PH LCD reactive power controller works automatically in 4-quadrant operation (generator operation), i.e. even with energy recovery to the utility company network, missing compensation power is detected without a problem and compensated.
Page 9
By using an additional digital input, it is possible to activate a second deviating target CosPhi. Furthermore, the device is equipped with a RS485 bus interface for operation at the KBR eBus with the visual energy computer software. This enables comfortable visualization of the measuring values and the control- ler's operating state as well as convenient configuration of the device via the primary control unit.
KBR multicomp F144-3PH Connecting the multicomp Note A phase-phase measurement (2 measuring phases without neutral conductor) is not possible with this device. For mixed operation of contactor stages and thyristor stages, the thyristor stages are detected if the discharge time set is under 1 second.
Connecting the multicomp KBR multicomp F144-3PH Caution The control voltage as well as the applied measuring voltage of the device must be protected by means of a back-up fuse. When connecting the current transformers, the energy flow direction and the correct assignment to the voltage path must be observed!
Connecting the multicomp KBR multicomp F144-3PH Terminal assignment Terminal: 1 (L) and 2 (N): Power supply connection A control voltage is required to supply the device with power. The unit is equipped with a multi-range power sup- ply and may be supplied by voltages of 85 – 265V AC/DC (see nameplate for device voltage).
Page 14
Temperature sensor input A temperature sensor, e.g. PT1000, can be connected to this input to measure the switchgear cabinet temperature. Temperature measuring range from -10°C to +60°C. 90 (earth) Interface connection For communication at the KBR eBus 91 (A) 92 (B): V2.00...
Connecting the multicomp KBR multicomp F144-3PH Basic controller settings (default settings): Methods of measurement: 3-phase Commissioning: Measuring voltage transformer: Primary voltage 400 V Ph-Ph Secondary voltage 400 V Ph-Ph Zero-point creator: Main current transformer: Primary current 1000 A Secondary current 5 A Rotary field I: 0°...
Page 16
KBR multicomp F144-3PH Connecting the multicomp Basic system parameters switching performance: Hysteresis connection: 100% of smallest stage power Hysteresis disconnection: 100% of smallest stage power Alarm delay: 1200 seconds (20 minutes) Idle time: 10 seconds Switching interval: 8 seconds Attenuation coefficient for current:...
Page 17
Connecting the multicomp KBR multicomp F144-3PH Miscellaneous: Scanning frequency Automatic Error message dialog In case of any errors, message and alarm relay Service: Password: No password (9999, meaning all functions are accessible) LCD parameters, scanning frequency, password, bus parameters and language set- tings are unaffected by reset.
KBR multicomp F144-3PH Control and display panel Control and display panel Navigation bar 9 10 11 12 13 14 15 16 17 18 of the display A A A A A A A A A A A A A A A A A A cos Ó...
Control and display panel KBR multicomp F144-3PH Description of general settings: Attenuation (DC) Reduction of the display fluctuations, the mea- suring cycle of the controller is not influenced. Idle time (t idle) Starts at compensation. After the idle time has expired, the next switching action follows.
This display is used for the initial commissioning of the controller, where all the necessary settings can be made. Controller preconfigured: If a controller already integrated into a KBR compensation unit by default should be used, only the parameters of the current transformer have to be configured.
Page 21
Start-up guideline KBR multicomp F144-3PH 2. Function test After all values have been programmed, a function test should be performed. To do so, the controller has to be taken off the voltage supply for a few seconds. After re-connecting it to the voltage supply, the controller has to start auto- matically.
KBR multicomp F144-3PH Start-up guideline After re-connecting it to the voltage supply, the controller has to start auto- matically. If the cosφ voltage is read in the cosφ act. menu immediately after switching it on, the value for cosφ should be low and inductive. After approx. 60 seconds, the controller starts to switch on the individual capacitor stages.
Start-up guideline KBR multicomp F144-3PH Setting transformer ratio After pressing the buttons, the following is displayed in the hot key area: Main current trans- Menu description former ENTER Display hot-key area Return for configuration Menu selection Menu selection...
Page 24
KBR multicomp F144-3PH Start-up guideline If the setting was changed, the following appears in the hot-key area of the display: Display hot-key area Enter value Continue to next digit Saving the last changes Leave setting menu without saving V2.00...
Operating structure KBR multicomp F144-3PH Menu overview main menu sub menu act.missing comp.power target cos phi act. cos phi target L1, L2, L3 act. cos phi max. Q act.missing comp.power miss power frequency voltage L1, L2, L3 L1, L2, L3...
Page 26
KBR multicomp F144-3PH Operating structure voltage transformer primary voltage secondary voltage measurement transformers zero-point creator voltage transformer three-phase sampling rate current transformer one-phase current transformer primary current secondary current target cosinus phi phase type I (one-phase target cosine 1 measurement method)
Page 27
Operating structure KBR multicomp F144-3PH switching hyst. switch on hysteresis ( % ) switch off hysteresis ( % ) switch. perform. switching hysteresis switching times switching times damping coeff. rest period damping coeff. voltage error mess. delay current switching delay react.
KBR multicomp F144-3PH Main menu cos φ Main menu cos φ First menu line 9 10 11 12 13 14 15 16 17 18 Second menu line A A A A A A A A A A A A A A A A A A Third menu line cos Ó...
Page 29
Main menu cos φ KBR multicomp F144-3PH Display as example: Main menu: = cosφ actual (instantaneous) Stage mode: = all stages automatic on Menu description: = cosφ actual (instantaneous) Measured cosφ: = 0.64 inductive Missing compensation power: = 22.4 kvar...
KBR multicomp F144-3PH Main menu voltage / current 4.6.1 Main menu voltage / current 9 10 11 12 13 14 15 16 17 18 A A A A A A A A A A A A A A A A A A U actual UÇ...
Main menu temperature KBR multicomp F144-3PH 4.6.2 Main menu temperature 9 10 11 12 13 14 15 16 17 18 A A A A A A A A A A A A A A A A A A temperature temp 28.7 °C...
Main menu power KBR multicomp F144-3PH 4.6.3 Main menu power 9 10 11 12 13 14 15 16 17 18 A A A A A A A A A A A A A A A A A A apparent power S L1 14.1...
KBR multicomp F144-3PH Main menu Uh voltage harmonics 4.6.5 Main menu Uh voltage harmonics 9 10 11 12 13 14 15 16 17 18 A A A A A A A A A A A A A A A A A A harm.
KBR multicomp F144-3PH Main menu Uh voltage harmonics 4.6.7 Main menu Ih current harmonics 9 10 11 12 13 14 15 16 17 18 A A A A A A A A A A A A A A A A A A harm.
Submenu KBR multicomp F144-3PH Sub menus 4.7.1 The Methods of measurement submenu contains the following items: 1. Single-phase measurement 2. 3-phase measurement 4.7.2 The Commissioning submenu contains the following items: 1. Transformer settings (voltage, current) a. Voltage transformer i. Primary voltage ii.
Page 40
KBR multicomp F144-3PH Submenu In the 700 V variant, this also serves to adapt the measuring voltage to the de- vice. Make sure that the device is configured for the operation with a zero-point creator. Transformers are available in the following variants:...
Submenu KBR multicomp F144-3PH 4. Max. switching capacity Setting ranges: Max. switching capacity per switching operation 0 to 999999 kVar 4.7.3 The Settings submenu contains the following items: 1) Display / language i) LCD parameters (a) LCD contrast (b) LCD brightness...
Page 42
KBR multicomp F144-3PH Submenu 2. Switching times i. Idle time ii. Alarm delay iii. Switching interval 3. Attenuation coefficients i. Voltage ii. Current iii. Qmiss (b) Temperature parameters 1. Activate measurement 2. Switching thresholds i. Switching on fan ii. Switching off fan iii.
Page 43
Submenu KBR multicomp F144-3PH Operating cycle limit 0 to 999999 THD limit 0 to 100%, (0% = deactivated) I d limit 0 to 100%, (0% = deactivated) Reset parameters Reset to factory settings (default settings) The temperature parameters contain the general activation and deactivation of the temperature measurement and the switching behavior resulting from this.
KBR multicomp F144-3PH Submenu 4) Service i) Password ii) Firmware version Setting ranges: Password 4-digits, numerical (9999, meaning all functions are accessible) Under the item Password, changes to the controller parameters can be password-protected. The password can be any 4-digit number code.
Notes on detecting errors KBR multicomp F144-3PH Messages that have to be deleted manually are shown under Error states. This guarantees that messages relevant to the correct operation of the system do not go unnoticed. The following status messages are displayed:...
KBR multicomp F144-3PH Maintenance System and safety devices maintenance In order to ensure proper function and a long service life of your system, per- form the following checks after commissioning and subsequently once a year! Check and retighten all connections. Screw connections may become loose ...
Technical data KBR multicomp F144-3PH Technical data multicomp F144-3PH Measuring and display values Voltage Units [V, kV;] display is switched automatically Display range 0 V to 999 kV Measuring range 3-phase 25 … 230 … 280 VAC, 50 / 60 Hz...
Compensa- Switching capacity 250V (AC) / 2A potential-free tion stage relay Serial interface RS 485 for connection to the KBR eBus or Modbus connection Transmission speed Max. 38400 Baud Bus protocol KBR eBus; a maximum of 32 devices per bus...
KBR multicomp F144-3PH Technical data Electrical connection Connection elements Plug terminals Permissible cross section of the connection Max. 2.5 mm at 5 mm steps, 1,5 mm lines 3.5 mm steps Measuring Fuse protection max. 6 A voltage input Measuring Fuse protection...
KBR multicomp F144-3PH Setting ranges 7.10 setting ranges Primary voltage 1 V to 999999 V Ph-Ph Secondary voltage 1 V to 999999 V Ph-Ph Zero-point creator On, Off Scanning frequency Auto, 50 Hz, 60 Hz Primary current 1 A to 999999 A ...
Data point description for the Modbus protocol KBR multicomp F144-3PH multicomp F144-3PH APPENDIX: Data point description for the Modbus protocol Changing the bus protocol ...56 Supported Modbus commands ...59 Data formats ........59 Interface parameters......61 Device settings ........62 Data points ..........69 Device information ......74...
KBR multicomp F144-3PH Data point description for the Modbus protocol 1 Changing the bus protocol The display appears if you press the button. 9 10 11 12 13 14 15 16 17 18 A A A A A A A...
Page 57
KBR multicomp F144-3PH Start the entry with the button and then change the bus protocol with switching from KBR eBus to Modbus. 9 10 11 12 13 14 15 16 17 18 A A A A A A A Bus parameters...
Page 58
KBR multicomp F144-3PH Data point description for the Modbus protocol Use the button to call up the Modbus settings. 9 10 11 12 13 14 15 16 17 18 A A A A A A A ModB settings e38.4 Para Addr.
Data point description for the Modbus protocol KBR multicomp F144-3PH 2 Supported Modbus commands 0x04 Read input registers 0x2B Read device identification The multicomp F144-3PH does not support broadcast commands. All described Modbus commands are device-specific commands. 3 Data formats (unsigned) short: 0x1234 Address Contents 0x12...
Page 60
KBR multicomp F144-3PH Data point description for the Modbus protocol Example 1: -12.5 decimal = 0xC1480000 hex M: 24 bit-mantissa E: Exponent with offset of 127 S: Sign for mantissa (S=1 neg.; S=0 pos.) Address Format SEEEEEEE EMMMMMMM MMMMMMMM MMMMMMMM...
KBR multicomp F144-3PH Data point description for the Modbus protocol 5 Device settings The settings are read with the 0x04 command (read input registers) in accordance with table 1. Writing is not possible at the moment. Address Words Description Value...
Page 63
Data point description for the Modbus protocol KBR multicomp F144-3PH Address Words Description Value Format 0xD026 2 free float 0xD028 2 Time (not available) unsigned long 0xD02a 2 Factor for default response times (not avail- unsigned able) long 0xD02c 2...
Page 64
KBR multicomp F144-3PH Data point description for the Modbus protocol Address Words Description Value Format 0xD052 2 Percentage of smallest available stage before 70-150 unsigned stages can be switched off long 0xD054 2 Alarm relay (not in use) unsigned long...
Page 65
Data point description for the Modbus protocol KBR multicomp F144-3PH Address Words Description Value Format 0xD06E Output index... unsigned long 0xD082 Type of connection: unsigned long 0xD084 Output index... unsigned long 0xD098 Type of connection: unsigned long 0xD09A Output index...
Page 66
KBR multicomp F144-3PH Data point description for the Modbus protocol Address Words Description Value Format 0xD11E Output index... unsigned long 0xD132 Type of connection: unsigned long 0xD134 Output index... unsigned long 0xD148 Type of connection: unsigned long 0xD14A Output index...
Page 67
Data point description for the Modbus protocol KBR multicomp F144-3PH Address Words Description Value Format 0xD1CE 2 Output index for the following stage param- unsigned eters (addresses 0xD1D0 to 0xD1E2) long 0xD1D0 2 Type (not in use) unsigned long 0xD1D2 2...
Page 68
KBR multicomp F144-3PH Data point description for the Modbus protocol Address Words Description Value Format 0xD28C 2 Light load limit [A] incl. current transformer 0.01 – float 9999.99 0xD28E 2 Average current limit [A] L1 1 – 9999 float 0xD290 2 Average current limit [A] L2 1 –...
Data point description for the Modbus protocol KBR multicomp F144-3PH 6 Data points Data points can be read via the command 0x04 (read input registers) in accordance with table 1. Address Words Description Unit Format 0x0002 Voltage PH-N L1 float...
Page 70
KBR multicomp F144-3PH Data point description for the Modbus protocol Address Words Description Unit Format 0x0044 Voltage 5th harmonic L1 float 0x0046 Voltage 5th harmonic L2 float 0x0048 Voltage 5th harmonic L3 float 0x004a Voltage 7th harmonic L1 float 0x004c...
Page 71
Data point description for the Modbus protocol KBR multicomp F144-3PH Address Words Description Unit Format 0x008c Current 9th harmonic L1 float 0x008e Current 9th harmonic L2 float 0x0090 Current 9th harmonic L3 float 0x0092 Current 11th harmonic L1 float 0x0094...
Page 72
KBR multicomp F144-3PH Data point description for the Modbus protocol Address Words Description Unit Format 0x0334 Relay states (20 Bit: Bit 0 = stage 1 bitwise unsigned ... Bit 17 = stage 18 // Bit 18 = error message //...
Page 73
Data point description for the Modbus protocol KBR multicomp F144-3PH Example Modbus RTU Request: 01 04 00 1F 00 32 40 19 in which Device address Command 00 1F Read active power L1 from register 0x0020 (in accordance with the Mod-...
KBR multicomp F144-3PH Data point description for the Modbus protocol xx xx xx xx Voltage 3rd harmonic L1 xx % xx xx xx xx Voltage 3rd harmonic L2 xx % xx xx xx xx Voltage 3rd harmonic L3 xx %...
Page 75
Data point description for the Modbus protocol KBR multicomp F144-3PH in which Device address Command MEI type (see Modbus definition) “Basic identification” (see Modbus definition) “Conformity level” (see Modbus definition) No further information follows (no additional telex required) Next object ID...
Page 76