Phasor measurement unit RES670 ANSI
Customized
Product version: 1.2
• Status indication LEDs.
• Alarm indication LEDs, which consist of 15 LEDs (6 red
and 9 yellow) with user printable label. All LEDs are
configurable from PCM600.
• Liquid crystal display (LCD).
• Keypad with push buttons for control and navigation
purposes, switch for selection between local and remote
control and reset.
• Isolated RJ45 communication port.
ANSI12000179 V1 EN
Figure 2.
Example of medium graphic HMI

15. Station communication

IEC 61850-8-1 communication protocol
The IED is equipped with double optical Ethernet rear ports for
IEC 61850-8-1 station bus communication. The IEC 61850-8-1
communication is also possible from the optical Ethernet front
port. IEC 61850-8-1 protocol allows intelligent electrical devices
(IEDs) from different vendors to exchange information and
simplifies system engineering. Peer-to-peer communication
ABB
according to GOOSE is part of the standard. Disturbance files
uploading is provided.
DNP3.0 communication protocol
An electrical RS485 and an optical Ethernet port is available for
the DNP3.0 communication. DNP3.0 Level 2 communication
with unsolicited events, time synchronizing and disturbance
reporting is provided for communication to RTUs, Gateways or
HMI systems.
Multiple command and transmit
When 670 IED's are used in Substation Automation systems
with LON, SPA or IEC60870-5-103 communication protocols
the Event and Multiple Command function blocks are used as
the communication interface for vertical communication to
station HMI and gateway and as interface for horizontal peer-to-
peer communication (over LON only).
IEC 62439-3 Parallel Redundant Protocol
Redundant station bus communication according to IEC
62439-3 Edition 1 and IEC 62439-3 Edition 2 are available as
options in 670 series IEDs. IEC 62439-3 parallel redundant
protocol is an optional quantity and the selection is made at
ordering. Redundant station bus communication according to
IEC 62439-3 uses both port AB and port CD on the OEM
module.

16. Hardware description

Hardware modules
Power supply module PSM
The power supply module is used to provide the correct internal
voltages and full isolation between the terminal and the battery
system. An internal fail alarm output is available.
Binary input module BIM
The binary input module has 16 optically isolated inputs and is
available in two versions, one standard and one with enhanced
pulse counting capabilities on the inputs to be used with the
pulse counter function. The binary inputs are freely
programmable and can be used for the input of logical signals
to any of the functions. They can also be included in the
disturbance recording and event-recording functions. This
enables extensive monitoring and evaluation of operation of the
IED and for all associated electrical circuits.
Binary output module BOM
The binary output module has 24 independent output relays
and is used for trip output or any signaling purpose.
Static binary output module SOM
The static binary output module has six fast static outputs and
six change over output relays for use in applications with high
speed requirements.
1MRK511254-BUS B