ABB RES670 Product Manual page 25

Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Phasor measurement unit RES670 ANSI
Customized
Product version: 1.2
Table 9. BIM - Binary input module with enhanced pulse counting capabilities
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V
48/60 V
125 V
220/250 V
Counter input frequency
Balanced counter input frequency
Oscillating signal discriminator
Maximum 176 binary input channels may be
activated simultaneously with influencing
factors within nominal range.
Table 10. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
Number of outputs
Impedance open state
Test voltage across open contact, 1 min
Current carrying capacity:
Continuous
1.0s
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF :
0.2s
1.0s
Breaking capacity for DC with L/R ≤ 40ms
Operating time
ABB
Rated value
16
24/30 V
48/60 V
125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
10 pulses/s max
40 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Static binary output trip
48 - 60 VDC
6
~300 kΩ
No galvanic separation
5A
10A
30A
10A
48V / 1A
60V / 0.75A
<1ms
1MRK511254-BUS B
Nominal range
-
RL ± 20%
RL ± 20%
RL ± 20%
RL ± 20%
-
-
-
110 - 250 VDC
6
~810 kΩ
No galvanic separation
5A
10A
30A
10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
<1ms
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents