ABB RES670 Product Manual page 52

Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Phasor measurement unit RES670 ANSI
Customized
Product version: 1.2
Inverse characteristic
Table 66. ANSI Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
td
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1651 V1 EN
Reset characteristic:
t r
=
×
t
td
(
)
2
-
I
1
EQUATION1652 V1 EN
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
52
Range or value
td = (0.05-999) in steps of 0.01
A=28.2, B=0.1217, P=2.0 , tr=29.1
A=19.61, B=0.491, P=2.0 , tr=21.6
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02, tr=4.85
A=64.07, B=0.250, P=2.0, tr=30
A=28.55, B=0.712, P=2.0, tr=13.46
A=0.086, B=0.185, P=0.02, tr=4.6
1MRK511254-BUS B
Accuracy
-
ANSI/IEEE C37.112, 5%
+ 40 ms
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents