ABB RES670 Product Manual page 53

Hide thumbs Also See for RES670:
Table of Contents

Advertisement

Phasor measurement unit RES670 ANSI
Customized
Product version: 1.2
Table 67. IEC Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
td
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1653 V1 EN
I = I
/I
measured
set
Time delay to reset, IEC inverse time
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
td
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1654 V1 EN
Reset characteristic:
TR
=
×
t
td
(
)
PR
-
I
CR
EQUATION1655 V1 EN
I = I
/I
measured
set
ABB
Range or value
td = (0.05-999) in steps of 0.01
(0.000-60.000) s
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
td = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
1MRK511254-BUS B
Accuracy
-
± 0.5% of set time ± 10 ms
IEC 60255-151, 5% + 40
ms
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents