Dedicated Instructions And Programming; Dedicated Instructions; Dedicated Instruction List, Applicable Devices, And Precautions - Mitsubishi LJ61BT11 User Manual

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

9. DEDICATED INSTRUCTIONS AND PROGRAMMING

9.1 Dedicated Instructions

9.1.1 Dedicated instruction list, applicable devices, and precautions

Target station
Master station
Local station
Intelligent
G(P).RISEND
device station
9
Master station
G(P).RLPASET
9 - 1
The following explains precautions on dedicated instructions and programming.
Using dedicated instructions, the L series master/local module is capable of the
following:
• Transient transmission to local stations and intelligent device stations
• Message transmission to remote device stations
(1) Dedicated instruction list
The following table lists the dedicated instructions that can be used for each of
these stations:
Instruction
Reads data from the buffer memory or the programmable
G(P).RIRD
controller CPU device of the specified station.
Writes data into the buffer memory or the programmable
G(P).RIWT
controller CPU device of the specified station.
G(P).RIRD
Reads data from the buffer memory of the specified station.
G(P).RIWT
Writes data into the buffer memory of the specified station.
Automatically performs handshaking with the specified
station and reads data from the buffer memory of that
G(P).RIRCV
station.
Available for modules that have signals for the handshake
(e.g. AJ65BT-R2N).
Automatically performs handshaking with the specified
station and writes data into the buffer memory of that
station.
Available for modules that have signals for the handshake
(e.g. AJ65BT-R2N).
Reads data in the automatic update buffer of the specified
station.
G(P).RIFR
Available for modules that have the automatic update buffer
(e.g. AJ65BT-R2N).
Writes data into the automatic update buffer of the specified
station.
G(P).RITO
Available for modules that have the automatic update buffer
(e.g. AJ65BT-R2N).
Sets the network parameters for the master station and
starts up the data link.
9. DEDICATED INSTRUCTIONS AND PROGRAMMING
Description
Reference
Section 9.1.2
Section 9.1.3
Section 9.1.2
Section 9.1.3
Section 9.1.4
Section 9.1.5
Section 9.1.6
Section 9.1.7
Section 9.1.8
9 - 1