17. Technical data

Table 5.
Dimensions
Relay type Description
Width
Height
Depth
Weight
Table 6.
Power supply
Description
Uaux nominal
Uaux variation
Burden of auxiliary voltage supply under
quiescent (Pq)/operating condition
Ripple in the DC auxiliary voltage
Maximum interruption time in the auxiliary
DC voltage without
resetting the relay
Table 7.
Energizing inputs
Description
Rated frequency
Current inputs
8
Value
frame
130.0 mm
case
121.5 mm
frame
160.0 mm
case
151.5 mm
151.5 mm
01.43 kg
Value
24...240 V AC, 50 and 60 Hz
24...240 V DC
85...110% of Uaux (20.4...264 V AC)
70...120% of Uaux (16.8...288 V DC)
< 5.0 VA
Max 12% of the DC value (at frequency of 100 Hz)
50 ms at Uaux rated
Rated current, I
n
Thermal withstand capability:
 Continuously
 For 1 s
Dynamic current withstand
 Half-wave value
Input impedance
1MDB07221-YN
Issued: 2017-05-09
Revision: A
Value
50/60 Hz
1/5 A
20 A
500 A
1250A
< 20 m Ω