ABB REJ601 Product Manual page 11

Relion 605 series feeder protection and control / feeder protection
Hide thumbs Also See for REJ601:
Table of Contents

Advertisement

Feeder protection and control / Feeder protection
REF601 / REJ601
Product version: 2.2FP2
Table 14.
Environmental tests
Description
Dry heat test (humidity < 50% )
 Working
 Storing
Dry cold test
 Working
 Storing
Damp heat test, cyclic
Damp heat test, steady state
Table 15.
Electromagnetic compatibility tests
Description
1 MHz/100 kHz burst disturbance test:
 Common mode
mode
Differential
Electrostatic discharge test:
 Contact discharge
Air discharge
Radiated, electro-magnetic field immunity
test
Fast transient disturbance tests:
All ports
Surge immunity test:
 Common mode
Differential mode
11
Type test value
 96 h at +70°C
 96 h at +85°C
 96 h at -25°C
 96 h at -40°C
 2 cycles (12 h + 12 h)
at +25°C...+55°C,
Rh > 93%
 96 h at +40°C,
humidity,
Rh > 93%
Type test value
2.5 kV, 1MHz, 400 pulses/s
1.0 kV, 1MHz, 400 pulses/s
6 kV, 150 pF/330 Ω
8 kV, 150 pF/330 Ω
10 V/m
f=80-1000 MHz, 1.4-2.7 GHz
10 V/m
f=80, 160, 450, 900 MHz,
900 PM, 1850 PM, 2150 PM
4 kV, 5.0 kHz
4.0 kV, 1.2/50 µs
2.0 kV, 1.2/50 µs
1MDB07221-YN
Issued: 2017-05-09
Revision: A
Reference
IEC 60068-2-2
IEC 60068-2-48
IEC 60068-2-1
IEC 60068-2-48
IEC 60068-2-30
IEC 60068-2-78
Reference
IEC 61000-4-12, class III
IEC 60255-22-1
IEC 60255-22-2, class III
IEC 61000-4-2
IEC 60255-22-3, class III
IEC 61000-4-3
IEC 60255-22-4, class A
IEC 61000-4-4
IEC 60255-22-5
IEC 61000-4-5
ABB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref601