Table 16.
Electromagnetic compatibility tests, continue
Description
Power frequency magnetic field immunity
test:
 Continuous
Short duration ( 1 s )
Conducted radio frequency interference
tests:
AC Voltage dips and short interruptions:
DC Voltage dips and short interruptions
Power frequency immunity test:
 Common mode
Differential mode
Pulse magnetic field immunity tests:
Emission tests:
Conducted
150 kHz-0.5 MHz
0.5 MHz-30 MHz
Radiated
30-230 MHz
230-1000 MHz
Table 17.
Insulation tests
Description
Dielectric test
Test voltage
Impulse voltage test
Test voltage
Insulation resistance test
Isolation resistance
12
Type test value
100 A/m
1000 A/m
10 V
f=150 KHz...80 Mhz
30% / 25 period
60% / 10 periods
100% / 2.5 periods
100% / 250 periods
30% / 500 ms
60% / 200 ms
100% / 50 ms
100% / 5000 ms
300 V rms
150 V rms
1000 A/m, 6.4/16 μs
< 66 dB ( μV/m)
< 60 dB ( μV/m)
< 40 dB ( μV/m)
< 47 dB ( μV/m)
Type test value
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 μs, 0.5 J
> 100 M Ω at 500 V DC
1MDB07221-YN
Issued: 2017-05-09
Revision: A
Reference
IEC 61000-4-8
IEC 60255-22-6, class III
IEC 61000-4-6
IEC 61000-4-11
IEC 61000-4-29
IEC 60255-22-7, Class A
IEC 61000-4-9
IEC 60255-25
EN 55011-CISPR II
Reference
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27
IEC 60255-5
IEC 60255-27