ABB REJ601 Product Manual page 9

Relion 605 series feeder protection and control / feeder protection
Hide thumbs Also See for REJ601:
Table of Contents

Advertisement

Feeder protection and control / Feeder protection
REF601 / REJ601
Product version: 2.2FP2
Table 8.
Binary input
Description
Rated voltage
Operating range
Current drain
Power consumption/input
Input sensing time
Trip-circuit supervision (TCS): (BI2)
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
Table 9.
Double-pole power output (XK2 : BO2)
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/R<40
ms, at 48/110/220 V DC
(two contacts connected in series)
Minimum contact load
Table 10.
Single-pole power output relay (XK10 : BO1)
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time constant L/R<40
ms, at 35 / 220 V DC
Minimum contact load
9
1MDB07221-YN
Issued: 2017-05-09
Value
24...240 V AC / DC
85...110% of Un for AC and
70...120% of Un for DC
2...20 mA
<0.5 W
25 ms
48...250 V AC / DC
~ 1.5 mA
20V AC / DC (15...20 V)
Value
240 V AC/DC
8 A
15 A
30 A
5 A / 3 A / 1 A
100 mA at 24 V AC/DC
Value
240 V AC/DC
8 A
15 A
30 A
5 A/ 0.2 A
100 mA at 24 V AC/DC
Revision: A
ABB