LCP100 Local Control Panel
August 2017
Table 2. Electromagnetic Immunity Performance Criteria
Port
Phenomenon
Electrostatic discharge (ESD)
Enclosure
Radiated EM field
Burst (fast transients)
I/O signal/control
Surge
Conducted RF
Specification limit = ±1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Figure 2. Fisher LCP100 Local Control Panel Dimensions
E1077‐1
4
Basic Standard
IEC 61000‐4‐2
IEC 61000‐4‐3
IEC 61000‐4‐4
IEC 61000‐4‐5
IEC 61000‐4‐6
129
(5.1)
Test Level
$4 kV contact
$8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
$1 kV, I/O lines
$2 kV, DC power lines
$1 kV, I/O lines
$2 kV, DC power lines)
150 kHz to 80 MHz at 3 Vrms with 1 kHz AM at 80%
94
(3.7)
110
(4.3)
Instruction Manual
D103272X012
Performance
Criteria
194
257
(7.6)
(10.1)
mm
(INCH)
(1)
A
A
A
A
A