LCP100 Local Control Panel
August 2017
Figure 13. Ex ic IIC or Ex tb IIIC Wiring Diagram 3
LCP100
Protection Method
Power Source
Ex ic IIC
Ex tb IIIC
LOOP
TERMINALS:
Ui = 27 VDC
Ii
= N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
2
NOTES:
 1  THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100
WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
 2  REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012)
FOR SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 11
16
LCP100
Wiring Order from
Logic Solver
LOOP
LCP100 then DVC6200 SIS
Instruction Manual
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point
INTRINSICALLY
SAFE
BARRIER
D103272X012
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1