Emerson Fisher LCP100 Instruction Manual page 23

Local
Hide thumbs Also See for Fisher LCP100:
Table of Contents

Advertisement

Instruction Manual
D103272X012
Figure 20. Ex ia IIB or Ex tb IIIC Wiring Diagram 4
LCP100
Protection Method
Power Source
Ex ia IIB
Ex tb IIIC
LOOP
AUX
TERMINALS:
TERMINALS:
Ui = 30 VDC
Ui = 30 VDC
Ii
= 226 mA
Ii
= 452 mA
Pi = 1.4 W
Pi = 1.4 W
Ci = 0.22 mF
Ci = 0 mF
Li = 16.0 mH
Li = 0 mH
2
NOTES:
 1  THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
 2  REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012) FOR
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 18
LCP100
Wiring Order from
Logic Solver
LOOP
LCP100 then DVC6200 SIS
LCP100 Local Control Panel
DVC6200 SIS Mode
(Current or Voltage)
Multi-Drop
INTRINSICALLY
SAFE
BARRIER
LC340 LINE
CONDITIONER
August 2017
LOGIC SOLVER
OUTPUT
24 VDC
(USER SUPPLIED)
1
23

Hide quick links: