Figure 11. Ex ic IIC or Ex tb IIIC Wiring Diagram 1
LCP100
Protection Method
Power Source
Ex ic IIC
Ex tb IIIC
NOTES:
1 THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100 WHEN
POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
2 REFER TO THE DVC6200 SERIES QUICK START GUIDE (D103556X012) FOR
SCHEMATICS AND ENTITY PARAMETERS.
GE26881-Sheet 9
14
LCP100
Wiring Order from
Logic Solver
LOOP
DVC6200 SIS then LCP100
LOOP
TERMINALS:
Ui = 27 VDC
Ii
= N/A
Pi = N/A
Ci = 1.1 nF
Li = 0 mH
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point
INTRINSICALLY
SAFE
BARRIER
2
Instruction Manual
D103272X012
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1