Emerson Fisher LCP100 Instruction Manual page 10

Local
Hide thumbs Also See for Fisher LCP100:
Table of Contents

Advertisement

LCP100 Local Control Panel
August 2017
Figure 7. Ex e mb [ib] IIC or Ex tb IIIC Wiring Diagram 3
LCP100
Protection Method
Power Source
Ex e mb [ib] IIC
Ex tb IIIC
2
NOTES:
 1  THE LOGIC SOLVER MINIMUM OUTPUT MUST BE 8 mA. THE LCP100 WHEN
POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA.
 2  FOR FLAMEPROOF/EXPLOSION-PROOF APPROVED DIGITAL VALVE CONTROLLERS,
INSTALL CONDUIT SEALS OR FLAMEPROOF CABLE GLANDS AS REQUIRED TO MAINTAIN
THE FLAMEPROOF/EXPLOSION-PROOF INTEGRITY OF THE DEVICE
GE26881-Sheet 5
10
LCP100
Wiring Order from
Logic Solver
LOOP
LCP100 then DVC6200 SIS
Instruction Manual
DVC6200 SIS Mode
(Current or Voltage)
Point-to-Point
D103272X012
LOGIC SOLVER
OUTPUT
8 - 20 mA
(USER SUPPLIED)
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents