2-2-3

E5ED Terminal Block Wiring Example

 Terminal Arrangement
The terminals block of the E5ED is divided into five types of terminals: control outputs 1 and 2, sensor input,
auxiliary outputs, input power supply, and options.
Input Power Supply
Control outputs 1 and 2
Auxiliary Outputs
Precautions for Correct Use
When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If a
different sensor is used, an input error (s.err) will occur. Check the setting of the Input Type
parameter.
Control Outputs 1 and 2
 Model Numbers
The control outputs 1 and 2 specifications of the E5ED are given in the following location in the model number.
E5ED-@@ @ @ @ M-@@@
Code
RX
1 relay output
QX
1 voltage output (for driving SSR)
CX
1 linear current output
QR
1 voltage output (for driving SSR) and
1 relay output
RR
2 relay outputs
E5@D Digital Temperature Controllers User's Manual (H224)
1
2
3
4
5
6
7
8
9
10
11
12
Control outputs 1 and 2
Output type
Not used.
25
13
14
26
Options
15
27
16
28
17
29
18
30
19
31
20
32
21
33
22
34
Sensor input
23
35
24
36
250 VAC, 5 A (resistive load)
12 VDC, 40 mA
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω max.
12 VDC, 21 mA for voltage output
250 VAC, 5 A (resistive load) for relay output
250 VAC, 5 A (resistive load)