Description of the system

Site requirements
System specifications
Model
Watts BTU
/
hour
CloudBoost
487
1662
100 with 12
drives
Storage capacity
This section includes site requirements, product specifications, and descriptions of
front and rear panels.
The site requirements are:
The system requires 2U of vertical space in a standard 19", four-post rack. Do not
l
use a two-post rack.
Use air conditioning that can cope with the maximum BTU/hour thermal rating.
l
Temperature control required with a gradient (change) not to exceed 30° C in an
l
hour.
In a closed or multi-unit rack, ensure that the unit has adequate airflow through
l
the front bezel and back panel and that ambient temperature requirements are
met.
Ensure that the front bezel and back panel clearances are met.
l
Ensure that cables at rear of unit do not obstruct exhaust airflow.
l
If installing in a closed cabinet, ensure that the front and rear doors have at least
l
65% open area to ensure adequate airflow for cooling.
Front bezel requires 1.56 inches (4.0 cm) of unobstructed clearance.
l
Back panel requires 5 inches (12.7 cm) of unobstructed clearance.
l
AC power outlets must be provided with an earth ground conductor (safety
l
ground). A safe electrical earth connection must be provided to each power cord.
Required voltage: 100-120 V~ or 200-240 V~. Frequency: 50 to 60 Hz.
l
Table 2 Fundamental features
Power (VA)
Size
(120V/230V)
(U)
502 (4.18A/
2
2.18A)
Operating temperature: 50° to 95° F (10° to 35° C), derate 1.1° C per 1000 feet,
l
above 7500 feet up to 10,000 feet.
Operating humidity: 20% to 80%, non-condensing.
l
Non-operating temperature: -40° to +149° F (-40° to +65° C).
l
Operating acoustic noise: Sound power, LWAd, is 7.52 bels. Sound pressure,
l
LpAm, is 56.4 dB. (Declared noise emission per ISO 9296.)
The table lists the capacities of the CloudBoost 100 system. EMC system internal
indexes and other product components use variable amounts of storage, depending on
Power
Weight
connectors
2 x grounded,
73 lb. /
120 VAC, NEMA
33.1 kg.
15P/R
System Installation and Setup Guide
Width
Depth
Height
19 in. /
29.5 in. /
3.5 in. /
48.3 cm.
74.9 cm.
8.9 cm.
Description of the system